Thursday, April 10, 2008

M & E > Tower Specification



Introduction

PSD is considering to purchase and erect Steel Structure Telecommunication Towers as per the attached Annex

1. TOWER SHALL MEET AND COMPLY WITH THE FOLLOWING STANDARDS REQUIREMENTS :
  • Towers shall meet and comply with all relevant International Standards including but not limited to EIN11A-222-E, F Or equivalent European Standards.
  • Tower shall be designed by or under the direct supervision of a registered profession & engineer, specifically experienced in the design of microwave towers. All design and analysis computations and installation drawings shall be certified and stamped by a licensed Professional Engineer.
  • Required Tower shall be, angled, galvanized, self-supporting type and require
    low maintenance, low maintenance.
  • The Contractor shall employ a quality control program that will ensure that
    engineering, fabrication, erection and relevant activities meet the requirements
    of this specification.
  • Contractor is required to provide complete erected Tower and also complete
    plans, assembly drawings which summarize the Tower components and
    foundation specifications, other documentation showing the necessary
    marking and details for the proper assembly and installation of the material
    including the design yield strength of the structural members and the grade of
    Structural bolts which to be used.
  • Manufacturer is required to fill in and sign the compliance list provided with
    tender, the compliance list will be considered as a vital part of project
    documents.
  • All documents relevant to this project shall be printed in English Language.
  • The life cycle of the Tower shall be 50 years minimum.

2. GENERAL REQUIREMENTS :

  • All hardware must be hot dipped galvanized in accordance with the Provisions
    of ASTM A-153 or equivalent.
  • Wind load, to be designed for a basic wind speed of 160 kilometers Per hour.
  • Antenna loading: As per Annex 1.
  • Tower shall be designed, as defined in EI4AJTIA- 222. Ice load shall be
    included on the Tower structure, antennas’ appurtenances, wave guides and
    transmission lines.
  • Tower sections shall be of bolted construction to permit in- service
    replacement of members. Shop welding shall be kept to a minimum and field
    welding is not permitted.
  • Twist angle permitted shall be less than 0.25 degree.
  • All K-braced or reversed K-braced sections shall be designed to include a
    structurally stable configuration of internal bracing at the midpoint of
    horizontal members.
  • Connections shall be detailed and designed to minimize stresses attributable to
    eccentricity
  • High strength bolts confirming to relevant international standards (e.g. ASTM
    A-325 or A -449) shall be used in all calculated load carrying connections All
    threaded fasteners shall be of adequate length that a minimum of two threads
    shall protrude beyond the nut or locking device when the nut is properly
    tensioned.
  • Space of 3 mm or greater between parallel or crossing members shall be filled
    with single thickness plates or ring fills. Stacked washers shell not be used for
    any reason for this purpose.
  • Hardened flat washers shall be provided for all oversized of slotted holes.
  • Anchor bolts shall be designed such that their projection above the concrete
    allows for one leveling nut below and two full-sized nuts above the base plate
    of the tower.
  • Under no circumstances shall ‘dissimilar metals’ be used in contact with one
    another.


3. DESIGN CALCULATIONS AND DRAWINGS
  • Three complete sets of the Tower drawings, one set of the tower grounding
    system and one set of design calculations for each tower shall be furnished to
    PSD in print and electronic form All submittals must bear a Professional
    Engineer’s stamp.
  • The Contractor shall submit structural calculations, foundation, and erection
    drawings for each Tower site location. Complete structural calculations are
    required covering all parts of the structures and all relevant items. Actual
    stresses and corresponding allowable stresses shall be listed for the vertical,
    diagonal and, girt members of the tower twist, sway, and displacement
    calculations shall be Made and identified for each microwave antenna. When
    computer printouts form a portion of the calculations, the Contractor shall
    include sufficient information to allow an independent engineer to thoroughly
    review the design.
  • The drawings include the station name, tower height, manufacturer’s name,
    manufacturer’s model number, antenna path azimuths, and elevation and plan
    views of the tower indicating the tower orientation In addition, the Contractor
    shall furnish section assembly drawings showing all tower members with their
    part numbers, splice plates, ladder mounting details, bolt sizes and types, and
    any other Information necessary to identify each Tower component.
  • Grounding system Drawing shall provide detailed information about the
    grounding system, showing lengths, elements dimensions, elements
    connectivity, quantities, layout and method of interconnection with shelter
    grounding system. All pertinent requirements of above sections of this specification are
    applicable to the towers accessories listed in following sections

4. CLIMBING LADDER:
  • Climbing ladder and climbing devices shall be provided.
  • Provisions shall be made and all material pervaded for the installation of an
    internal climbing ladder from the base to the tower top. The rung width shall
    be at least 40.0 cm with the step diameter being a minimum of 1.6 cm; the
    maximum adjacent rung spacing shall be 40.0 cm. The step spacing shall be
    uniform throughout the ladder length.


5. WAVE GUIDE SUPPORT

  • Waveguide Ladder, Provisions shall be made and all material pervaded for the
    installation of an internal waveguide ladder from the base to tower top. These
    ladders shall provide secure support coax runs for at least 10 runs of coax
    along the tower length. The ladders have 0.9 to 1.2 meters rung spacing.
  • Waveguide Bridge (Cable Tray) shall provide support and protection of
    waveguide to equipment shelter, Tower and shelter are 5 to 8 meters apart.
  • Waveguide support structures shall be grounded in accordance with the tower
    grounding specification.


6. CONNECTIONS AND LOCKING DEVICES

  • All members shall be connected with galvanized structural bolts unless
    otherwise approved by PSD.
  • The contractor shall provide bolts, nuts and lock washers in a quantity 5% in
    excess of the actual bolt count, for each size required for each Tower.
  • All towers will be provided with the correct size and length of anchor bolts
    necessary to carry the anticipated Tower loads. If the Tower loads require
    more than one bolt per leg, they shall be shop welded into a cluster to
    eliminate the need for a template during field installation.
  • All threaded fasteners shall extend not less than 2 threads beyond nuts and
    locking devices.


7. REST PLATFORMS

  • Rest platforms shall be placed at intervals 15 meters.(45M/60M Towers Only)
  • A rest platform will consist of a level platform of grating which allows room
    for two persons.
  • Safety hand rails shall be provided around the rest platforms.
  • Work platforms with safety hand rails shall be provided around Microwave
    antennas.


8. TOWER LIGHTNG

  • Obstruction lighting systems shall be supplied with the towers and installed as
    required CAA.
  • An electronic device equipped with a photoelectric cell that change over lights
    on and off automatically from dawn till dusk and provide alarms indicating
    beacon or/and power failure.
  • Obstruction lighting system shall be capable of indicating when light is turned
    on or off.
  • Contractor shall submit schematic, installation drawing and specifications of
    the obstruction light system he is providing.


9. GROUNDING AND LIGHTNING PROTECTION

  • Towers shall have a complete grounding system which conforms to the
    minimum requirements of EIA RS-222-F, “Protective Grounding”.
  • The grounding system of tower shall achieve a resistance to earth less than 5
    ohm.
  • The grounding system of tower shall be interconnected with shelter grounding
    system to provide a common ground potential to the communications site.
    This shall include lightning protection, electric service and antenna system
    ground.
  • The grounding system may consist of, but is not limited to, the following
    components:


    - Tower ground ring.
    - Ground radials.
    - Grounding electrodes.
    - Tower ground bus bar.
    - External ground bus bar.

  • Tower ground ring shall be buried and encircles the tower structure and
    provide a means of bonding ground rods together and bonding other
    grounding electrode system components together.
  • The Tower ground bus bar shall be an integral part of the tower construction
    or vertical waveguide ladder it should be large enough to accommodate all
    coaxial cable connections and connection to the grounding electrode system.
    The tower ground bus bar shall be physically and electrically connected to the
    Tower, it shall be installed below the transmission line ground kits, near the
    area of the tower at the point where the antenna transmission lines transition
    from the tower to the shelter.
  • Near end ground bus bar shall be installed at the point where the antenna
    transmission lines enters the shelter (or building), and shall be connected to
    the external ground ring using the straightest possible downward run of 35
    mm2 csa (#2 AWG) or larger bare solid or stranded tinned copper conductor,
    it should be large enough to accommodate all coaxial connections and
    connection to the grounding electrode System PSD.
  • Each leg of the towers shall be bonded to the tower ground ring using
    grounding conductors of 35 mm2 csa (#2 AWG) minimum, bare tinned solid
    or stranded copper conductor.
  • Tower grounding system shall be connection ready to be interconnected with
    shelter (or building) ground.
  • Exothermically welding shall be used for connecting grounding system
    elements, other methods of connection shall not be used.
  • Each tower must be equipped with a lightning rod fastened at the extreme top
    of the tower, the lightning rod shall be made of galvanized steel, with
    minimum dimensions of 1.6 cm diameter by 1.2 meter long, shall be attached
    so as to extend a minimum of 45 cm above the highest point of the tower,
    including all attachments.


10. Tower Base Excavations:

  • All excavation works shall conform to relevant Jordanian codes.
  • The contractor shall insure that each foundation excavation is accurately
    located, sized and plumbed as specified on the drawings.
  • All topsoil shall be separately removed and stockpiled for rater use in the final
    Back-filling process. No waste from excavations shall be spread on the
    property without the approval of the PSD. Excavated material, unsuitable or
    not required for Back-filling shall be removed from the site and disposed of
    by the Contractor in local authorities Specified dump areas.
  • Site Safety Measures & Tools are the responsibility of the contractor.
    Excavation shall not be left open .


11. Tower Base Foundations :

  • All materials, cement, fine aggregate, coarse aggregate, water and admixtures
    shall conform to relevant Jordanian codes.
  • Foundation designs shall be based upon the soil characteristics and parameters
    listed in the site geotechnical report supplied by PSD.
  • Foundation shall be designed for maximum structure reaction resulting from
    the specific loads.
  • Foundation drawings shall indicate structure reactions, material strengths,
    dimensions, reinforcing steel and embedded anchorage material type, size and
    location.
  • Foundation shall use ready-mix concrete, concrete shall conform to standards
    and codes adopted in Jordan.
  • All concrete construction methods shall conform to the standards practiced
    and adopted in Jordan or equivalent international standard.
  • The contractor shall submit a detailed report of material specifications used in
    Concrete Mix Design.
  • o ensure uniform production of concrete, representative samples will be
    taken at the request of and under the supervision of the PSD engineer and
    contractor assigned engineer for the purpose of making cubes for strength
    tests. All tests shall conform to standards and codes adopted in Jordan.
  • In case the concrete placed by the contractor is determined, by testing "to be
    defective or not accepted" in any way, the contractor shall be responsible and
    at his expense for one of the following courses of action which shall be
    determined by PSD:


    - Removal and replacement of all defective concrete.
    - The cost of design and construction changes necessary to incorporate the
    inferior concrete.

  • All reinforcement shall conform to relevant Jordanian codes. All
    reinforcement cages, anchor bolts, anchor rods, etc. Shall be accurately
    positioned and secured while concrete is being poured and vibrated. Exposed
    portions of anchor bolts shall be coated with tape or heavy grease prior to
    pouring concrete. The contractor shall provide All bar supports, ties, spacers
    and other materials required to keep the reinforcing in its proper position.
  • Heating of rebar in order to bend it and welding of rebar will not be permitted.
  • The portion of concrete surfaces exposed above grade shall be fair faced
    concrete.


12. BACKFILL
  • All backfill works shall conform to relevant Jordanian specifications.
  • Material for backfill shall be furnished by the Contractor from the excavated
    site material to the extent available. Additional backfill ‘similar to the site
    material, shall be furnished by the Contractor where required. If excavated
    material is not suitable as backfill, Contractor will replace it with acceptable
    material.
  • Fill materials shall be placed in horizontal layers of 25cm lifts and each layer
    compacted with vibrating compactors such as tampers ‘rammers, or vibro
    plates to 95% modified proctor density.
  • The finished grade at backfilled and other disturbed areas shall conform to the
    lines and grades of the site. Areas around buildings and towers shall be graded
    so as to cause surface water to flow away from them.


13. TOWER ERECTION
  • The contractor shall furnish all necessary personnel, supervision ‘tools,
    equipment and transportation required to complete the installation and
    erection of all items specified herein.
  • Any Tower elements which sustain damage shall be reported to PSD.
  • Correction of damage shall not be done by contractor without the approval of
    PSD.
  • The actual location of the tower and other structures will be determined by
    PSD, Tower orientation shall be agreed upon later on between PSD and the
    contractor.
  • The Structural members shall be accurately set to lines and evasions indicated
    on the erection drawings, also the various members forming each tower bay
    shall be aligned and adjusted before permanently fastening.
  • The contractor shall maintain a check of Tower plumpness during all phases
    of the erection work. Plumpness shall be measured by means of a transit
    placed so that the sight elevation angles are less than 45 degrees. At least two
    sights shall be made for each check, oriented at right angles to each other and
    taken within the shortest practical time interval. At all times the tower shall be
    plumb within the tolerance specified in drawings. After completion of tower
    construction, with all joints tight, and all appurtenances installed ‘the
    contractor shall make a final check of tower plumpness in the manner
    prescribed above
  • Field modifications including welding or burning of holes in members are not
    acceptable.
  • Contractor shall provide a dedicated, full-time field supervisor. This
    contractor-employee will be assigned and available through all phases of
    construction. Responsibilities will include, but not be limited to: verification
    of tower and anchor locations; finished grade and construction of foundations;
    delivery and erection of tower; off-Load location and joint inspection of
    construction.


14. CLIMBING TOOLS

Contractor is required to provide as an option a recommended list of climbing
tools e.g. full body harness, safety blocks, rescue and retrieval system, shock
absorbers


15. INSTRUCTIONS FOR CONTRACTOR

Contractor Shall provide complete erected functioning 60 meter towers
according to specifications and requirements listed in this document.

No comments:

Answer Bag